Three-phase Automatic Battery Chargers

[cs_content][cs_element_section _id=”1″ ][cs_element_row _id=”2″ ][cs_element_column _id=”3″ ][cs_element_image _id=”4″ ][/cs_element_column][cs_element_column _id=”5″ ][cs_element_text _id=”6″ ][cs_content_seo]The ABC-series of three phase chargers are a completely solid state, automatic and of the constant voltage type having:

AC voltage compensation
DC voltage regulation
Full current limit
Filtered DC output (ABC32)
Three phase AC input

Two rate charging is standard. A control switch allows selection of float-automatic, or high rate charge. With optional Auto-Charge, in the automatic mode, the charger will high rate charge the battery whenever it is discharged.
The three phase charger will raise the voltage to the high rate setting and maintain this level for a timed interval. Recharge of the battery is accomplished without excessive over or undercharging.
The ABC-series float chargers are fully current limited. If current demands exceeds the chargers rating, the output voltage drops rapidly, protecting the charger and the system to which it is connected. The chargers fuses or breakers will not trip during such overload conditions.\n\n[/cs_content_seo][/cs_element_column][/cs_element_row][cs_element_row _id=”7″ ][cs_element_column _id=”8″ ][cs_element_text _id=”9″ ][cs_content_seo]Request More Information

Standard Features

Conservative component selection and design assures long life
LEDs for AC-ON, and high rate charge AC input 3-pole breaker
AC and DC surge protection Float / high rate control switch DC voltmeter & ammeter 2% Precise voltage regulation Fully current limited
AC input breaker and DC output fuse Reverse battery protection
Natural convection cooling Modular construction

Options

DC 2-pole breaker instead of fuse Precision metering
Extra filter (Use ABC32)
Battery temperature compensation AC failure alarm relay
Multi-Alarm Monitor includes four alarms & LEDs with common relay for High DC volts, Low DC volts, Rectifier failure and Ground fault.
Separate alarm relays may be specified. Precision metering
Auto-Charge Control or manual timers Audible alarm
Drip Shields
CE compliance and marking Many other accessories available

Specifications
InputVoltage: 208, 240, 380, 480 or other Phase: ThreeFrequency: 50 or 60 Hertz
OutputVoltage: 24, 32, 48, 120, 240 or other nom.Current: From 15 to 600 ampsRegulation: +/- 1/2% from no load to full load, with +/- 10% AC line variationABC32 types have filtering to 100mv RMS with 4X battery connected
Operating TeperatureFrom +14oF (-10oC) to +122oF (+50oC)
AdjustmentsInternal potentiometers for float, high rate and current limit
ProtectionAC input breakerDC output fuse or optional breaker Automatic current limitingAC surge suppressor Slow start circuitry Reverse battery protection
VentilationNatural convection cooling
CabinetsANSI #61 light gray paint Nema 1 typeWall or floor mounting
Standard ControlsFloat/high rate switch for manual controlStandard Displays AC-On LED
Models

With Standard Filter
With Extra Filter

Model
Output
Case Size

WT LBS

 
Model
Output
Case Size
WT LBS

Volts
Amps
Volts
Amps

ABC31
-24
-50
W3
150
 
ABC32
-24
-50
G1
170

ABC31
-24
-75
G1
250
 
ABC32
-24
-75
G1
275

ABC31
-24
-100
G1
325
 
ABC32
-24
-100
G1
370

ABC31
-24
-125
G1
375
 
ABC32
-24
-125
G1
425

ABC31
-24
-150
G1
425
 
ABC32
-24
-150
G1
475

ABC31
-24
-200
G1
480
 
ABC32
-24
-200
G2
550

ABC31
-24
-250
G2
525
 
ABC32
-24
-250
G2
600

ABC31
-24
-300
G2
655
 
ABC32
-24
-300
G2
700

ABC31
-24
-400
G2
700
 
ABC32
-24
-400
G3
780

ABC31
-24
-500
G3
775
 
ABC32
-24
-500
G3
850

ABC31
-24
-600
G3
825
 
ABC32
-24
-600
G3
925

ABC31
-48
-50
G1
200
 
ABC32
-48
-50
G1
260

ABC31
-48
-75
G1
290
 
ABC32
-48
-75
G1
350

ABC31
-48
-100
G1
400
 
ABC32
-48
-100
G1
460

ABC31
-48
-125
G1
440
 
ABC32
-48
-125
G2
500

ABC31
-48
-150
G1
475
 
ABC32
-48
-150
G2
550

ABC31
-48
-200
G2
575
 
ABC32
-48
-200
G2
650

ABC31
-48
-250
G2
675
 
ABC32
-48
-250
G3
750

ABC31
-48
-300
G2
775
 
ABC32
-48
-300
G3
860

ABC31
-48
-400
G3
850
 
ABC32
-48
-400
G3
950

ABC31
-48
-500
G2D
1200
 
ABC32
-48
-500
G2D
1350

ABC31
-48
-600
G2D
1350
 
ABC32
-48
-600
G2D
1500

ABC31
-120
-25
G1
240
 
ABC32
-120
-25
G1
300

ABC31
-120
-35
G1
300
 
ABC32
-120
-35
G1
360

ABC31
-120
-50
G1
425
 
ABC32
-120
-50
G1
500

ABC31
-120
-75
G1
475
 
ABC32
-120
-75
G2
550

ABC31
-120
-100
G2
600
 
ABC32
-120
-100
G2
680

ABC31
-120
-125
G2
675
 
ABC32
-120
-125
G2
750

ABC31
-120
-150
G2
830
 
ABC32
-120
-150
G2
910

ABC31
-120
-200
G3
1000
 
ABC32
-120
-200
G3
1100

ABC31
-120
-250
G3
1250
 
ABC32
-120
-250
G2D
1400

ABC31
-120
-300
G2D
1350
 
ABC32
-120
-300
G2D
1500

ABC31
-120
-400
G2D
1450
 
ABC32
-120
-400
G2D
1650

ABC31
-120
-500
G2D
1600
 
ABC32
-120
-500
G2D
1820

ABC31
-120
-600
G2D
1700
 
ABC32 
-120
-600
G3D
1950

ABC31
-240
-15
G1
290
 
ABC32
-240
-15
G1
350

ABC31
-240
-25
G1
425
 
ABC32
-240
-25
G1
510

ABC31
-240
-35
G1
475
 
ABC32
-240
-35
G1
560

ABC31
-240
-50
G1
500
 
ABC32
-240
-50
G2
590

ABC31
-240
-75
G2
800
 
ABC32
-240
-75
G2
890

ABC31
-240
-100
G2
875
 
ABC32
-240
-100
G3
1000

ABC31
-240
-150
G3
1350
 
ABC32
-240
-150
G3
1480

ABC31
-240
-200
G3
1450
 
ABC32
-240
-200
G2D
1610

ABC31
-240
-250
G2D
1675
 
ABC32
-240
-250
G2D
1800

ABC31
-240
-300
G2D
1700
 
ABC32
-240
-300
G3D
1950

Dimensions

All dimensions in inches. Selection of some accessories require larger cabinets.

Case Size 
W3
G1
G2
G3
G2D
G3D

Height
28
40
53
74
53
74

Width
16
33
33
33
62
62

Depth
14
19
24
24
24
24

\n\n[/cs_content_seo][/cs_element_column][/cs_element_row][/cs_element_section][/cs_content]