Switch-Mode Battery Charger

[cs_content][cs_element_section _id=”1″ ][cs_element_row _id=”2″ ][cs_element_column _id=”3″ ][cs_element_image _id=”4″ ][cs_element_text _id=”5″ ][cs_content_seo]Model: ABC31SM\n\n[/cs_content_seo][/cs_element_column][cs_element_column _id=”6″ ][cs_element_text _id=”7″ ][cs_content_seo]For charging standby & on-line batteries
The new Three-Phase Automatic Battery Charger features a switch-mode design for high efficiency. The unit also features:

AC voltage compensation
DC voltage regulation
Full current limit
Filtered DC output

Three rate charging is standard. The charger will raise the voltage to the high rate setting and maintain this level for a timed interval at which point it will reduce to a safe float. Recharge of the battery is accomplished without excessive over or under charging.
The ABC-series chargers are fully current limited. If current demands exceeds the chargers rating, the output voltage drops rapidly, protecting the charger and the system to which it is connected. The chargers fuses or breakers will not trip during such overload  conditions.
Request More Information
\n\n[/cs_content_seo][/cs_element_column][/cs_element_row][/cs_element_section][cs_element_section _id=”8″ ][cs_element_row _id=”9″ ][cs_element_column _id=”10″ ][cs_element_text _id=”11″ ][cs_content_seo]STANDARD FEATURES
Conservative component selection and design assures long lifeLEDs for AC-ONAC and DC surge protectionDC voltmeter & ammeter 2%Precise voltage regulationFully current limitedAC input and DC output fusesReverse battery protectionForced air cooling, fans temperature and load controlledModular construction
OPTIONS
AC and DC 2-pole breakersPrecision meteringBattery temperature compensationAC failure alarm relayDC Failure Alarm RelayMulti-Alarm Monitor includes four alarms & LEDs with common relay High DC volts, Low DC volts, Rectifier failure and Ground fault.Audible alarmDrip ShieldsCE compliance and marking
[column type=”one-third”]
INPUTVoltage: 480V AC +/-15%Phase: ThreeFrequency: 50 or 60 Hertz
OUTPUTVoltage: 24 to 120V DCCurrent: From 20 to 240 ampsRegulation: +/- 1/2% from no load to full load,with +/- 15% AC line variationOutput Ripple: <1%4X battery connectedEfficiency: Up to 93%
OPERATING TEMPERATUREFrom -4oF (-20oC) to +122oF (+50oC)
PROTECTIONAC input fuse or optional breakerDC output fuse or optional breakerAutomatic current limitingAC surge suppressorSlow start circuitryReverse battery protection
VENTILATIONForced Air Cooling
CABINETSANSI #61 light gray powder coat14/18 guage steelWall or floor mounting
STANDARD DISPLAYSAC-ON LEDDC voltmeter and ammeter -2% accuracy
DIMENSIONS SPECIFICATIONS All dimensions in inches.CASE SIZE  W4Height  36Width   16Depth    16
[/column][column type=”two-thirds” last=”true”]

[/column][clear]\n\nSwitch-Mode Battery Charging Curves for American Battery Chargers[/cs_content_seo][/cs_element_column][/cs_element_row][/cs_element_section][/cs_content]